Miller Electric 230Volt Owner's Manual Page 26

  • Download
  • Add to my manuals
  • Print
  • Page
    / 106
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
OM-263 001 Page 22
5-10. Electrical Service Guide Filtair 12000
Elec Serv 201401
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard.
These recommendations are for a dedicated circuit sized for the rated output of the equipment.
60 Hz Three Phase
20 HP Motor
Input Voltage (V) 230
Input Amperes (A) At Rated Output 54.9
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
80
Normal Operating Fuses
3
−−
Min Input Conductor Size In AWG
4
4
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
4
8
Reference: 2014 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
Notes
Work like a Pro!
Pros weld and cut
safely. Read the
safety rules at
the beginning
of this manual.
Page view 25
1 ... 25 26 27 ... 106

Comments to this Manuals

No comments