OM-263 001 Page 21
5-8. Electrical Service Guide − Filtair 6000
Elec Serv 2014−01
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard.
These recommendations are for a dedicated circuit sized for the rated output of the equipment.
60 Hz Three Phase
10 HP Motor 15 HP Motor
Input Voltage (V) 230 230
Input Amperes (A) At Rated Output 28.9 42.9
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
40 60
Normal Operating Fuses
3
−− −−
Min Input Conductor Size In AWG
4
8 6
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
4
10 8
Reference: 2014 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
5-9. Electrical Service Guide − Filtair 8000
Elec Serv 2014−01
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard.
These recommendations are for a dedicated circuit sized for the rated output of the equipment.
60 Hz Three Phase
15 HP Motor 20 HP Motor
Input Voltage (V) 230 230
Input Amperes (A) At Rated Output 42.9 54.9
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
60 80
Normal Operating Fuses
3
−− −−
Min Input Conductor Size In AWG
4
6 4
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
4
8 8
Reference: 2014 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
Comments to this Manuals